KUAB Konsult & Utveckiing AB
Calibration Certificate
The Falling Weight Deflectometer (FWD) KUAB 50 with serial number FV123, owned by West Coast Road Masters OY, Fiiiland,manufactured by KUAB Konsult & Utveckiing AB in Sweden, was in February 2024 calibrated by KUAB's personnel. After the calibration the FWD FV123 measures with the same accuracy as a new KUAB 50 and meets all relevant standards, including but not limited to ASTM D4694 and the Swedish Method Description TRVMB 112. The result of the calibration was recorded in the configuration file FVO.INI in the laptop operating the FWD. The result of the calibration is also shown below. Descriptions of the calibration methods and the calculations giving these numbers are available at KUAB, email all(g),kuab.se.
KUAB STATIC SEISMOMETER CALIBRATION OUTPUT FILE FV123
Date: 15.2.2024 Time: 13:15:12 A/D converter b i t value C a l i b r a t i o n f a c t o r f o r C a l i b r a t i o n f a c t o r f o r C a l i b r a t i o n f a c t o r f o r C a l i b r a t i o n f a c t o r f o r C a l i b r a t i o n f a c t o r f o r C a l i b r a t i o n f a c t o r f o r C a l i b r a t i o n f a c t o r f o r C a l i b r a t i o n f a c t o r f o r
N/A mV/bit seismometer 0 seismometer seismometer seismometer seismometer seismometer seismometer seismometer
0.486541 pm/mV 0.4 622 66 pm/mV 0.461810 pm/mV 0.492542 pm/mV 0.4 66397 pm/mV 0.4 68841 pm/mV 0.4 44085 pm/mV 0.477430 pm/mV
SO SI S2 S3 S4 S5 Voltage at 3 25 -2597 -2769 -2725 -2510 -2619 -2712 Voltage at 3 50 -2087 -2237 -2189 -2008 -2087 -2180
P o s i t i o n 5.25 5.25 5.25 5.25 5.25 5.25 Voltage 1506 1542 1589 1535 1657 1545
Voltage at 3 25 -2598 -2772 -2728 -2508 -2623 -2711 Voltage at 3 75 -1574 -1695 -1654 -1508 -1552 -1645 Voltage at 3 75 -1574 -1695 -1654 -1505 -1552 -1645 Voltage at 4 25 -546 -615 -571 -489 -482 -585 Voltage at 4 75 482 468 513 525 591 484 Voltage at 5 25 1506 1542 1586 1535 1656 1546 Voltage at 5 75 2526 2618 2660 2547 2719 2611 Voltage at 6 25 3542 3687 3726 3551 3773 3661 Voltage at 6 75 4546 4746 4780 4541 4820 4703 Voltage at 7 25 5536 5797 5819 5526 5856 5730
S6 S7 DO Dl D2 D3 D4 05 D6 07 -2846 -2669 -2285 -2158
5.25 5.25 1629 1490
-2852 -2665 1729 -1632 -767 -786 -767 -745 -726 -773 -772 -785 1729 -1633 -767 -786 -7 67 -744 -726 -773 -773 -785 -611 -594 -266 -285 -265 -242 -226 -275 -273 -286 517 450 235 217 238 260 276 227 231 216 1628 1490 734 716 735 759 775 726 728 717 2745 2538 1231 1215 1233 1259 1272 1227 1227 1220 3853 3561 1726 1711 1728 1755 1765 1720 1722 1712 4939 4586 2216 2202 2216 2245 2254 2210 2207 2205 6008 5601 2698 2690 2698 2732 2739 2692 2685 2693
Calibration factor for seismometer 0 Calibration factor for seismometer 1 Calibration factor for seismometer 2 Calibration factor for seismometer 3 Calibration factor for seismometer 4 Calibration factor for seismometer 5 Calibration factor for seismometer 6 Calibration factor for seismometer 7
Calibration certificate page 1 of 2
= 0.487374 = 0.463954 = 0.463587 = 0.494386 = 0.467759 = 0.469823 = 0.446862 = 0.480853
KUAB Konsult & Utvec'-Jing AB
Box 10, 795 21 Rattvik, SwGd«
Postal address
Box 10 S-795 21 Rattvik Sweden
Teiephone
Nat 070 3344354 Int +46 70 3344354
e-mail/
Visiting address
Faluvagen 6 S-795 35 Rattvik Sweden
VAT number
SE556311352001
[loadmodel] description=2 + 2 buffers ForceThreshold=500 SensorThreshold=100 risetime=25 aload(l)=1209 aload(2)=3345 a]oad(3)=4083 aload(4)=5112 nominalload(l)=1200 nominalload(2)=3300 nominalload(3)=4000 nominalload(4)=5000 corfac(l)=.03 corfac(2)=.06 corfac(3)=.l corfac(4)=.12 defaultheight(l)=.024 defaultheight(2)=.202 defaultheight(3)=.289 defaultheight(4)=.470
[loadplatel] description=The small plate radius=15 calfac= 17496 sharpcalfac=l caladd=133 square=2580 [pavtemp] ;Rayomatic 14 / Optris CT available=True voltagefactor=.0025 lowestrange=-30 offset=0 xcoefficient(0)=0 xcoefficient(l)=130 xcoefficient(2)=0 xcoefficient(3)=0 xcoefficient(4)=0 [airtemp] calfac=0.998478155785319 caladd=-273.15 offset=0 lastdate=l 5.2.2024 lasttime=14:02:22
Rattvik 2024 04 23
Calibration certificate page 2 of 2
Postal address Telephone e-mail/ Visiting address VAT number
Box 10 S-795 21 Rattvik Sweden
Nat 070 3344354 Int +46 70 3344354
se Faluvagen 6 SE556311352001 S-795 35 Rattvik Sweden
From: Tiit Kaal <[email protected]>
Sent: Wed, 08 May 2024 12:44:09 +0000
To: Elmar Aruja <[email protected]>
Cc: Juha-Matti Vainio <[email protected]>
Subject: FWD mõõtmiste teostamise luba
KUAB Konsult & Utveckiing AB
Calibration Certificate
The Falling Weight Deflectometer (FWD) KUAB 50 with serial number FV123, owned by West Coast Road Masters OY, Fiiiland,manufactured by KUAB Konsult & Utveckiing AB in Sweden, was in February 2024 calibrated by KUAB's personnel. After the calibration the FWD FV123 measures with the same accuracy as a new KUAB 50 and meets all relevant standards, including but not limited to ASTM D4694 and the Swedish Method Description TRVMB 112. The result of the calibration was recorded in the configuration file FVO.INI in the laptop operating the FWD. The result of the calibration is also shown below. Descriptions of the calibration methods and the calculations giving these numbers are available at KUAB, email all(g),kuab.se.
KUAB STATIC SEISMOMETER CALIBRATION OUTPUT FILE FV123
Date: 15.2.2024 Time: 13:15:12 A/D converter b i t value C a l i b r a t i o n f a c t o r f o r C a l i b r a t i o n f a c t o r f o r C a l i b r a t i o n f a c t o r f o r C a l i b r a t i o n f a c t o r f o r C a l i b r a t i o n f a c t o r f o r C a l i b r a t i o n f a c t o r f o r C a l i b r a t i o n f a c t o r f o r C a l i b r a t i o n f a c t o r f o r
N/A mV/bit seismometer 0 seismometer seismometer seismometer seismometer seismometer seismometer seismometer
0.486541 pm/mV 0.4 622 66 pm/mV 0.461810 pm/mV 0.492542 pm/mV 0.4 66397 pm/mV 0.4 68841 pm/mV 0.4 44085 pm/mV 0.477430 pm/mV
SO SI S2 S3 S4 S5 Voltage at 3 25 -2597 -2769 -2725 -2510 -2619 -2712 Voltage at 3 50 -2087 -2237 -2189 -2008 -2087 -2180
P o s i t i o n 5.25 5.25 5.25 5.25 5.25 5.25 Voltage 1506 1542 1589 1535 1657 1545
Voltage at 3 25 -2598 -2772 -2728 -2508 -2623 -2711 Voltage at 3 75 -1574 -1695 -1654 -1508 -1552 -1645 Voltage at 3 75 -1574 -1695 -1654 -1505 -1552 -1645 Voltage at 4 25 -546 -615 -571 -489 -482 -585 Voltage at 4 75 482 468 513 525 591 484 Voltage at 5 25 1506 1542 1586 1535 1656 1546 Voltage at 5 75 2526 2618 2660 2547 2719 2611 Voltage at 6 25 3542 3687 3726 3551 3773 3661 Voltage at 6 75 4546 4746 4780 4541 4820 4703 Voltage at 7 25 5536 5797 5819 5526 5856 5730
S6 S7 DO Dl D2 D3 D4 05 D6 07 -2846 -2669 -2285 -2158
5.25 5.25 1629 1490
-2852 -2665 1729 -1632 -767 -786 -767 -745 -726 -773 -772 -785 1729 -1633 -767 -786 -7 67 -744 -726 -773 -773 -785 -611 -594 -266 -285 -265 -242 -226 -275 -273 -286 517 450 235 217 238 260 276 227 231 216 1628 1490 734 716 735 759 775 726 728 717 2745 2538 1231 1215 1233 1259 1272 1227 1227 1220 3853 3561 1726 1711 1728 1755 1765 1720 1722 1712 4939 4586 2216 2202 2216 2245 2254 2210 2207 2205 6008 5601 2698 2690 2698 2732 2739 2692 2685 2693
Calibration factor for seismometer 0 Calibration factor for seismometer 1 Calibration factor for seismometer 2 Calibration factor for seismometer 3 Calibration factor for seismometer 4 Calibration factor for seismometer 5 Calibration factor for seismometer 6 Calibration factor for seismometer 7
Calibration certificate page 1 of 2
= 0.487374 = 0.463954 = 0.463587 = 0.494386 = 0.467759 = 0.469823 = 0.446862 = 0.480853
KUAB Konsult & Utvec'-Jing AB
Box 10, 795 21 Rattvik, SwGd«
Postal address
Box 10 S-795 21 Rattvik Sweden
Teiephone
Nat 070 3344354 Int +46 70 3344354
e-mail/
Visiting address
Faluvagen 6 S-795 35 Rattvik Sweden
VAT number
SE556311352001
[loadmodel] description=2 + 2 buffers ForceThreshold=500 SensorThreshold=100 risetime=25 aload(l)=1209 aload(2)=3345 a]oad(3)=4083 aload(4)=5112 nominalload(l)=1200 nominalload(2)=3300 nominalload(3)=4000 nominalload(4)=5000 corfac(l)=.03 corfac(2)=.06 corfac(3)=.l corfac(4)=.12 defaultheight(l)=.024 defaultheight(2)=.202 defaultheight(3)=.289 defaultheight(4)=.470
[loadplatel] description=The small plate radius=15 calfac= 17496 sharpcalfac=l caladd=133 square=2580 [pavtemp] ;Rayomatic 14 / Optris CT available=True voltagefactor=.0025 lowestrange=-30 offset=0 xcoefficient(0)=0 xcoefficient(l)=130 xcoefficient(2)=0 xcoefficient(3)=0 xcoefficient(4)=0 [airtemp] calfac=0.998478155785319 caladd=-273.15 offset=0 lastdate=l 5.2.2024 lasttime=14:02:22
Rattvik 2024 04 23
Calibration certificate page 2 of 2
Postal address Telephone e-mail/ Visiting address VAT number
Box 10 S-795 21 Rattvik Sweden
Nat 070 3344354 Int +46 70 3344354
se Faluvagen 6 SE556311352001 S-795 35 Rattvik Sweden
Nimi | K.p. | Δ | Viit | Tüüp | Org | Osapooled |
---|---|---|---|---|---|---|
Kiri | 09.05.2024 | 4 | 9.2-3/24/7992-2 | Valjaminev kiri | transpordiamet | ERC Konsultatsiooni Osaühing, Transpordiamet |